AVEVO ALP-LAS

Innovative Solutions

We produce central extraction systems for many different industries.

ALP-CES systems for plasma and laser cutting fumes ALP-LAS Our units are especially designed to absorb and filter the fumes generated on plasma and laser cutting tables. LAS Thanks to the compact structure of our series products, it allows them to be preferred as a central system for the suction of many different dust and fumes.

ALP-CES central filter systems are modularly designed. Number of filter modules and required flow/pressure as required.

They are installed by integrating with the fans to meet them. It has many different pollutants such as welding fumes, grinding dusts, metal dusts, plastic dusts, paper and food dusts, composite and fiber dusts. Can be used with various types of installation. They are products suitable for outdoor and indoor installations.

Example installation types:

  • Push-Pull system
  • Displacement (layered ventilation) system
  • System compatible with acrobat arms
  • Connection to grinding tables
  • Connection to hoods and cells (e.g. welding robot stations)
  • Connection to cutting tables
    And much more.


Some Applications:

  • Welding Fumes
  • Grinding dusts
  • Composite dusts
  • Plastic dusts
  • Metal dusts
  • GRP-Fiber dusts
  • Tobacco, paper, food processing dusts
  • Oil mist and emulsion vapors
  • Laser and plasma cutting fumes
  • Foundry industry
  • Dental powders
  • Soldering fumes
    And many other industrial pollutants

Applications

Files

Strengths

Order Codes

ALP LAS 4: 222.150.004
ALP LAS 6: 222.150.006
ALP LAS 8: 222.150.008
ALP LAS 10: 222.150.010

ALP LAS 4: Clever 222.150.1.004
ALP LAS 6: Clever 222.150.1.006
ALP LAS 8: Clever 222.150.1.008
ALP LAS 10: Clever 222.150.1.010

AVEVO ALP-CES 3000

Avevo™ ALP-CES 3000 Our fixed filter unit is designed in a compact structure. Height adjustable vibration damping feet provide a solid posture. Wheeled dust collection bucket is easy to access.
It can be used with various types of installation against many different pollutants such as welding smoke, grinding dusts, metal dusts, plastic dusts, paper and food dusts, composite and fiber dusts.
Suitable for internal installation.

Example installation types:

  • Welding Robot Cells
  • WAAM cells
  • Installation with acrobat extraction arms
  • Connection to grinding tables
  • Connection to hoods and cells
  • Connection to thermal cutting tables
    And much more…

Applications

Files

Strengths

Order Codes

ALP CES 3000: 600.001.017

AVEVO ALP-CES

TECHNICAL DATA

ALP-CES 1
Max air flow: 15.000 m³/h
Max filter cartridge: 6
Max filter surface: 140 m²
Filter cleaning: Jet-Pulse
Water proof: Yes
Dimensions (YxGxD) mm: 2500x1295x1300
Dust collector capacity: 147 liter

ALP-CES 2
Max air flow: 30.000 m³/h
Max filter cartridge: 12
Max filter surface: 280 m²
Filter cleaning: Jet-Pulse
Water proof: Yes
Dimensions (YxGxD) mm: 2500x1295x1300
Dust collector capacity: 294 liter

ALP-CES 3
Max air flow: 45.000 m³/h
Max filter cartridge: 18
Max filter surface: 420 m²
Filter cleaning: Jet-Pulse
Water proof: Yes
Dimensions (YxGxD) mm: 2500x3885x1300
Dust collector capacity: 441 liter

ALP-CES 1
Post cleaning: Yes
Spark arrester: Yes
Filter alarm: Yes
Body material: Galvanised steel
Sound pressure: 60-75 dB(A)
Electronic fan control: Optional

ALP-CES 2
Post cleaning: Yes
Spark arrester: Yes
Filter Alarm: Yes
Body Material: Galvanised steel
Sound pressure: 60-75 dB(A)
Electronic fan control: Optional

ALP-CES 3
Post cleaning: Yes
Spark arrester: Yes
Filter Alarm: Yes
Body Material: Galvanised steel
Sound pressure: 60-75 dB(A)
Electronic fan control: Optional

Applications

Files

Strengths

Order Codes

ALP CES 1 without fan&motor: 600.001.034
ALP CES 2 without fan&motor: 600.001.035
ALP CES 3 without fan&motor: 600.001.036

Hall Ventilation Solutions

ALP-Herd

Innovative Ambient Ventilation Concept

R&D studies were carried out entirely within our company.
The system ensures that all volatile particles formed in production areas are filtered to prevent scattering and that the ambient air reaches a breathable level.

HERD, which absorbs and filters the polluted air in the environment, adapts to the principle of displacement ventilation by returning some of the cleaned air to the environment at very low speeds at ground level.
Some of the cleaned air is blown towards the other HERD unit through jet nozzles and continuous mobilization of volatile particles is ensured.

Push-Pull Systems

In Push-Pull mixed ventilation, fresh air is delivered to the upper area of ​​the hall through jet nozzles that have the effect of mixing the air in the hall.

  • Hall height < 7.5 m
  • Low thermal loads; < 10 tons / year welding wire consumption
  • Feed nozzles with high jet range
  • Two pipelines opposite each other
  • Suitable for cooling and heating
  • Also designed for dust and odor

Upstream Layered Ventilation

In layered- or displacement ventilation, the clean area is fed through source vents close to the floor. This provides support for the thermal upswing of welding fumes.

  • Hall height ≥ 7,5 m
  • High thermal loads > 10 tons / year welding wire consumption
  • Displacement outlets close to the floor for generating a layer of cold air
  • Sensors for continuous temperature measurement and fully-automated control of the proportion of fresh air
  • Low air volume flows are sufficient
  • Suitable for cooling and heating
  • Acceptable heat loss.
  • Given appropriate thermal loss and suitable for dust and odour

Cell & Hood Smoke Extraction